Skip to main content
Loading…
This section is included in your selections.

Click here to view prior versions of this section.

The 2017 National Electrical Code is amended by the following modifications:

1. (A) Article 110.26(B) and 110.33(B); Add a new sentence following Sections 110.26(B) and 110.33(B) to read as follows:

Doors shall not open into the required working space. Exception: Residential occupancies.

B. Add to Article 110.26(A) and Article 110.33(A):

The required working space floor, platform or finished grade at the equipment, shall be of one level and reasonably flat.

C. Add to Article 210.8(A) to read as follows:

No lighting outlets shall be on any circuits which is required to be ground fault protected.

Add new item #4 to Article 210.52(B)(3):

4. Minimum size circuit to a disposal or a dishwasher shall be #12 copper, with a 20 amp. rated overcurrent device.

Add a sentence to Article 250.122:

All conduit installed on a roof of a structure must be installed with a grounding equipment conductor sized by table 250.122 NEC.

(Ord. M-4198 §4, 2017; Ord. M-3863 §17, 2008; Ord. M-3639, 2003; Ord. M-3378, 1998; Ord. M-2261 §5.08, 1981; Ord. M-2708 §5, 1987; Ord. M-2998 (part), 1992; Ord. M-3133 §2 (part), 1994)